丹富斯遙控浮球閥由主閥、針閥、球閥、浮球閥、微型過濾器等組成水力控制接管系統(tǒng),調(diào)定后,自動控制液面高度。遙控浮球閥直接利用液面控制,不需要其它裝置和能源,保養(yǎng)簡便,液面控制準確度高,不受水壓影響,密封可靠。100X遙控浮球閥產(chǎn)品廣泛用于高層建筑、生活區(qū)等供水管網(wǎng)系統(tǒng)的水塔、水池等設(shè)施的液面控制。 丹富斯遙控浮球閥性能、遙控浮球閥規(guī)格
丹富斯遙控浮球閥工作原理
當管道從進水端給水時,由于針閥、球閥、浮球閥是常開的,水通過微型過濾器、針閥、控制室、球閥、浮球閥進入水池,此時控制室不形成壓力,主閥開啟,水塔(池)供水。當水塔(池)的水面上升至設(shè)定高度時,浮球浮起關(guān)閉浮球閥,控制室內(nèi)水壓升高,推動主閥關(guān)閉,供水停止。當水面下降時,浮球閥重新開啟,控制室水壓下降,主閥再次開啟繼續(xù)供水,保持液面的設(shè)定高度。
丹富斯水利控制閥設(shè)計選用要點 丹富斯遙控浮球閥性能、遙控浮球閥規(guī)格
( 1 )工程式中應(yīng)用的水力控制閥是經(jīng)過制造廠檢驗合格,各種標識齊全,技術(shù)資料符合要求的產(chǎn)品。
( 2 )根據(jù)功能要求,選擇閥門種類,再根據(jù)管道輸送介質(zhì)、溫度、建筑標準和業(yè)主 要要求 等,確定閥門的閥體和密封部位的材質(zhì)。常用的閥體材料有鑄鐵 、銅鐵、銅、塑料等。常用的密封面和襯里材料有銅合金、塑料、鋼、硬質(zhì)合金、橡膠等。閥 體材料應(yīng)與管道材料相匹配。
( 3 )閥門的公稱壓力有0.6、1.0、1.6、2.5和4.0MPa等不同級別,管道輸送的介質(zhì),其工作壓力應(yīng)小于閥門的公稱壓力值。
( 4 )工程中水力控制閥的設(shè)置應(yīng)當有足夠的空間,以便管理、操作、安裝和維修,并應(yīng)符合管路對閥門的要求。
( 5 )管路采用法蘭連接時,應(yīng)采用法蘭連接的水力控制閥;管路采用溝槽式連接時,應(yīng)采用溝槽式連接的水力控制閥。
( 6 )水利控制閥應(yīng)設(shè)置在介質(zhì)單向流動的管路上。
( 7 )水利控制閥主閥體上的箭頭方向必須與管路系統(tǒng)流向*。
( 8 )接水力控制閥管段不 應(yīng)有氣堵 、氣阻現(xiàn)象。在管網(wǎng)zui高位置 等存氣段 應(yīng)設(shè)置自動排氣閥。
( 9 )閥門水平安裝時,閥蓋、閥桿應(yīng)朝上。垂 直安裝時,閥蓋、閥桿應(yīng)朝外。
( 10 )閥門安裝前應(yīng)做強度和嚴密性試驗。
( 11 )閥門的強度和嚴密性試驗應(yīng)符合以下規(guī)定。
A、閥門的強度試驗壓力為公稱壓力的1.5倍;
B、閥門的嚴密性試驗壓力為公稱壓力的1.5倍;
C、試驗壓力在試驗持續(xù)時間內(nèi)應(yīng)保持不變,且殼體填料及閥瓣密封面無滲漏;
D、閥門試驗持續(xù)時間按上表。
丹富斯遙控浮球閥主要技術(shù)參數(shù)
|
Dan fuss remote-controlled floating ball valve consists of the main valve, needle valve, ball valve, ball valves, hydraulic control micro filter, etc to take over the system, after setting, automatic control level. Remote control float valve directly using the liquid level control, and do not need other devices and energy sources, convenient maintenance, high accuracy of liquid level control, is not affected by water pressure, the sealing is reliable. 100 x remote-controlled floating ball valve products are widely used in high-rise buildings, living areas, such as water supply pipe network system of liquid level control of water tower, pool and other facilities.
Dan fuss remote-controlled floating ball valve working principle
When the pipeline from the inlet water supply, because of the needle valve, ball valve, floating ball valve is normally open, water through the micro filter, needle valve, control room, ball valve, floating ball valve into the pool, the control room not formation pressure, the main valve opens, supply water towers (pool). When a water tower (pool) rose to the surface of the setting height, floating ball float close floating ball valve, control indoor water pressure increases, promote the main valve closed, stop water supply. When the water drop, floating ball valve reopens, control the water pressure drop, the main valve to open again continue to water supply, set to keep the liquid surface height.
Dan fuss hydraulic control valve design and selection
(1) type in the application of hydraulic control valve is a factory inspection, all kinds of logo is complete, the product technical information to meet the requirements.
(2) according to the functional requirements, select the valve type, and then according to the pipeline medium, temperature, building standards and the owner to ask and so on, to determine the valve body and the material of sealing parts. Commonly used valve body materials have cast iron, copper, iron, copper, plastic, etc. Commonly used seal face and lining material have copper alloy, plastic, steel, cemented carbide, rubber, etc. The valve body material should match the piping material.
(3) the nominal pressure of the valve are 0.6, 1.0, 1.6, 1.0 and 1.6 MPa at different levels, such as pipeline medium, its working pressure should be less than nominal pressure value of the valve.
(4) of hydraulic control valves in the project should have enough space, so that the management, operation, installation and maintenance, and should accord with the requirement of pipe to the valve.
(5) pipe with flange connection, the flange connection of the hydraulic control valve should be adopted; Line using the groove connection, should adopt the groove connection of the hydraulic control valve.
(6) water control valve should be set on the road at the pipe of unidirectional flow medium.
Hydraulic control valve (7) the main direction of the arrow on the valve body must be consistent with the piping system flow.
(8) by the hydraulic control valve, gas section should not have air blocking resistance phenomenon. In the aeration pipe network highest position such as deposit Should be set up automatic exhaust valve.
(9) when mounted horizontally, the valve cover, stem should be facing up. Vertical installation, valve cover, stem should be outward.
(10) valve strength and leak test should be obtained before installation.
(11) the strength of the valve and leak test shall meet the following requirements.
A, the valve strength test pressure is 1.5 times the nominal pressure;
B, valve leak test pressure is 1.5 times the nominal pressure;
C, test pressure in the test duration shall remain unchanged, and shell packing and clapper sealing surfaces without leakage;
D, valve test duration according to the table.